Skip to content
Metering
Riyadh · School

Meters, daily use against budget, the last 24 hours, the water balance and zone statements.

This month
193m³
+15.1 % vs the same days last month
Cost at the 2027 price
Against budget
+17.8 %
Budget 421 m³ for July
Unaccounted water
11.5 %
22 m³
Last 30 days

m³ through the meter each day, against the daily budget

  • Water used
  • Daily budget
Last 24 hours

m³ an hour used in the building, without cooling make-up. The shaded band is the night window, 01:00 to 05:00.

  • m³ an hour
  • Night window

Lowest night use: 0.01 m³/h. A steady use at night, when the building is quiet, often means a leak.

Water balance, month to date

What came in, what the sub-meters saw, and what is left unaccounted: leaks and unmetered points.

m³Share
Inlet (utility meter)193.3100.0 %
Sum of sub-meters168.387.0 %
Change in stored water2.81.4 %
Unaccounted22.311.5 %

Zone statements, month to date

m³ × SAR 12 (2027 business price), for recharging tenants or departments.

Zonem³ShareAmount
Classrooms and toilets131.177.9 %SAR 1,573
Kitchen20.412.1 %SAR 244
Irrigation16.910.0 %SAR 202

Meters

From the utility meter to each sub-meter, today.

  • Utility meter0.0 m³
    • Inlet meter (clip-on)0.0 m³
      • Ground and roof tanks−0.0 m³ stored
        • Classrooms and toilets0.0 m³ 0 %
        • Kitchen0.0 m³ 0 %
        • Irrigation0.0 m³ 0 %
        • Unaccounted today0.0 m³

Changes compare the same days of last month. Budgets are set per building by the owner.