Alert · Hotel J1 · Jeddah

Cooling tower drain valve stuck open

FaultAssignedJ1-S7

What happened

The tower's drain valve is open. Water runs away.

Named by the rule “Drain open”: a simple rule, not AI.

Tank or line
Cooling tower
Since
Mon, 12 Jul 2027, 12:51
Alert raised
Mon, 12 Jul 2027, 14:06

Why the rule fired

Water ran through the drain in 5 readings in a row. Normally the drain opens for a few minutes, then closes.

Estimated loss

estimate

58.6 m³a day

a day

If an inspector finds it first

No fine for this fault in the 2027 rules.

Recommended action

Close the drain valve and check the controller that opens it.

Bill settlement

Evidence record

Dated proof for the inspector and for a bill settlement.

Photo before
Waiting
Photo after
Waiting
Invoice
Waiting
Technician sign-off
Waiting
Readings around the alert

Tower drain flow

Activity and notes

Every step with its time. Notes stay inside WFI and are not part of the inspector record.

  1. 12 Jul, 14:06

    Alert raised by the rule “Drain open”

  2. 12 Jul, 15:05

    Assigned to Technician A2; quote requested

  3. 12 Jul, 15:30

    Quote sent: SAR 1,450

  4. 12 Jul, 15:55

    Quote approved

Assign to a technician

Assigned to Technician A2 at 12 Jul, 15:05

Open the partner phone view

Quote

From Partner Firm A

Approved

Sent 12 Jul, 15:30

Visit and first reportSAR 350
PartsSAR 700
LabourSAR 400
Total (before VAT)SAR 1,450

Done in 1 working day · Valid for 7 days

The repair costs about 2 days of the estimated loss.

Approved 12 Jul, 15:55. Work can start.

Inspector warning

No warning received. If one comes, the 14-day window starts here.

Inspector record

A read-only link with the dated record, in English and Arabic.

AI insights

AI adds what the rules cannot do: small, slow problems and forecasts. It never replaces the rules.

Each model learns from this building's own history.

Early warning

AI

Learns this building's normal night and flags small, slow leaks the rules miss.

AI model
OKScore 0.2 · warning line 5

Nights look normal. The quietest flow at night is within the learned range.

Night flow above normal, 01:00–05:00

litres an hour above the learned normal; shaded: normal range from 28 nights

  • Above normal
  • Normal range

Busy nights (hotels) hide small leaks; this model is surest in buildings with quiet nights.

Pump health

AI

Reads the pump's current and spots wear, clogging or dry running before the pump fails.

AI model
OK

Current is normal: 0.7 % from the learned value.

Mean running current each day

Amperes; straight-line trend over the last 14 days

  • Current
  • Trend
  • Trip level

Tank forecast

AI

During a supply cut, predicts how many hours of water are left, so the owner can order a water tanker in time.

AI model
OK

City supply is flowing. The forecast starts when a cut is seen.

If the city supply stopped now, the stored water would last about:

44 hours

Range 38–57 hours · AI